101 | 1 | 109 |
下载次数 | 被引频次 | 阅读次数 |
本文以某柔性直流背靠背阀厅为研究对象,结合规范规定对阀厅的抗震性能目标提出要求。以抗震设防烈度8度(0.30g)作为地震输入条件,分别对采用钢支撑和粘滞阻尼器的阀厅结构进行地震响应分析,研究不同抗震方案下阀厅结构的抗震性能。研究结果表明:阀厅采用粘滞阻尼器方案,在为结构提供良好的耗能效果和降低地震加速度响应峰值的同时,具有良好的经济指标。
Abstract:The valve hall in a flexible DC back-to-back converter station is taken as the research object.Combined with the code,the objective requirements for the seismic performance of the valve hall are proposed.The seismic fortification intensity of 8 degree (0.30g) is taken as the seismic input condition,the seismic analysis of the valve hall is carried out with steel supports and viscous fluid dampers.And the seismic performances of these two different seismic schemes are studied.The results show that the schemes of viscous fluid damper can provide good energy dissipation effect for the valve hall,reduce the peak value of seismic acceleration response,and it has good economic benefit.
[1]中国电力企业联合会.电力设施抗震设计规范:GB50260—2013[S].北京:中国计划出版社,2013.
[2]中华人民共和国住房和城乡建设部.建筑抗震设计标准:GB/T50011—2010[S].
[3]陈寅,李志,朱东,等.考虑屈曲约束支撑的±1100kV阀厅抗震性能化设计研究[J].电力勘测设计,2021(5):7-11.
[4]陈寅,杜晓磊,夏正东.消能减震性能化设计在大型电力结构中的应用[J].建筑结构,2020,50(23):108-113.
[5]曹枚根,徐文汉,娄杨剑.特高压高端阀厅防屈曲支撑结构地震响应分析[J].南方电网技术,2020,14(9):17-23.
[6]徐文汉,曹枚根,唐志琼,等.特高压换流站低端阀厅隔震设计及地震响应分析[J].建筑结构,2020,50(增刊1):349-353.
基本信息:
DOI:10.13500/j.dlkcsj.issn1671-9913.2024.09.002
中图分类号:TM721.1
引用信息:
[1]刘素丽,陈寅,李志等.基于粘滞阻尼器的柔性直流背靠背阀厅消能减震分析[J].电力勘测设计,2024,No.198(09):5-9+16.DOI:10.13500/j.dlkcsj.issn1671-9913.2024.09.002.
基金信息:
中电工程科技项目:柔性直流换流站典型电气设备减隔震复合控制技术研究(DG2-T03-2022)