nav emailalert searchbtn searchbox tablepage yinyongbenwen piczone journalimg journalInfo journalinfonormal searchdiv searchzone qikanlogo popupnotification paper paperNew
您当前所在位置: 首页> 文献列表> 输电线路操作冲击空气间隙计算及适用范围
2021, 02, No.150 12-16
输电线路操作冲击空气间隙计算及适用范围
基金项目(Foundation):
邮箱(Email):
DOI: 10.13500/j.dlkcsj.issn1671-9913.2021.02.004
投稿时间: 2019-12-23
投稿日期(年): 2019
修回时间: 2020-09-08
终审时间: 2021-02-24
终审日期(年): 2021
审稿周期(年): 2
发布时间: 2021-02-28
出版时间: 2021-02-28
移动端阅读
摘要:

通过对国内外6处27组全比例模拟操作冲击空气间隙绝缘强度实验数据分析、比对,IEC71-2-1996方法与试验结果吻合度较高,进一步证明了现行"设计规范"提出的高海拔修正法可行,其海拔适用范围可扩大至4?500~5?000?m,针对IEC71-2-1996的海拔修正因子m曲线,提出了空气间隙拟合数字计算公式。

Abstract:

The article through studied and analyzed of 6 places at home and abroad 27 groups experimental data of full scale simulated tower switching impulse air clearance insulation strength.The method of IEC71-2-1996 is in good agreement with the experimental results.Through the analysis and comparison,it is proved that the high-altitude correction method proposed by the current design specifications is feasible,and the range of its altitude application can be extended to 4?500?m ~ 5?000?m.In addition,according to the "m" curve of IEC71-2,This paper puts forward the numerical formula,which is convenient for design and application.

参考文献

[1]IEC.Insulation coordination-part 2:Application guide:IEC71-2-1996[S].American:IEC,1996.

[2]EPRI.AC Transmission Line Reference Book-200?kV and Above,Third Edition[M].American:EPRI,2005.

[3]中国电力科学研究院.乡城—水洛500?kV交流输电线路杆塔空气间隙方电特性和间隙距离选择研究[R].北京:中国电力科学研究院,2011.

[4]西南电力设计院.交流输电线路外绝缘特性及高海拔修正设计技术研究[R].成都:西南电力设计院,2013.

基本信息:

DOI:10.13500/j.dlkcsj.issn1671-9913.2021.02.004

中图分类号:TM75

引用信息:

[1]周刚,聂国一,梁明,等.输电线路操作冲击空气间隙计算及适用范围[J].电力勘测设计,2021,No.150(02):12-16.DOI:10.13500/j.dlkcsj.issn1671-9913.2021.02.004.